PCS-9250 DC Electronic CT/VT
  • NR Electric provides DC electronic CT, electronic VT and DC filter electronic CT for double-line commutation converter (LCC) and voltage source converter (VSC-based) HVDC transmission projects. The DC electronic transformers have advantages of small size, light weight, and no ferromagnetic resonance problems.

  • DC Electronic CT DC Electronic VT DC Filter Electronic CT

    DC electronic CTs are intended for applications in HVDC converter stations. They measure DC current, harmonic current, and output digital signals for the protection and control devices in the converter station.

    • Configuration

    The DC electronic CTs are composed of the following four parts:

       Primary Sensor

    The primary sensor includes one current divider and one air core coil. The current divider is used to measure DC current and the air core coil is used to measure harmonic current.

       Remote Module

    DC electronic CTs have multiple identical remote end modules, which can backup each other to guarantee high reliability. The remote module receives and processes the output signals from the current divider and the air core coil. It outputs serial digital optical signals.

       Composite Insulator with Embedded Optical Fiber

    This insulator adopts the composite material, while several multimode optical fibers are embedded inside as signal transmission media.

       Merging Unit

    The merging unit is placed in control room. In one hand, it works as power supply for remote module by laser sending, in the other hand, it receives data from remote module. The output of merging units is sent to the protection and control devices using the specified protocol (IEC60044-8 protocol or TDM bus protocol). Merging units are connected to remote modules via optic fibers.

    • Features

    The highest voltage rate of DC electronic CT is 1100kV.

    The insulator adopts composite silica gel, with high reliability and light weight, and it is easy to transportation and installation.

    The diverter uses Manganin as a material, which has a good temperature stability.

    The structure of the sensor provides great performance in heat dissipation.

    The air-core coil is used here for harmonic current measurement, and the wide-frequency band can be obtained with good dynamic performance.

    The remote module uses redundant configuration with high reliability.

    16-bit A/D signals are adopted in the remote module with high precision.

    Laser power supply is used for remote modules with self-checking function.

    DC electronic VT is used to measure and transmit DC voltage signals to control and protection devices in the converter station. DC electronic VT consists of DC divider, resistor box, remote module and merging unit. The sampling data is sent to the merging unit in the control room via optical fiber.

    • Configuration

       DC Divider

    DC divider is composed of precise resistor and shunt capacitor, the former is used to measure DC voltage and the latter can achieve equalized voltage distribution and ensure its frequency characteristics

       Resistor Box

    The resistor box is a low voltage divider, which can convert the measured voltage to multiple channel signals sent to the remote module.

       Remote Module

    DC electronic VTs also have multiple identical remote end modules, which can backup each other to guarantee high reliability. The remote module receives and processes the output signals from the voltage divider, and it outputs serial digital optical signals.

       Merging Unit

    The merging unit is placed in control room. In one hand, it works as power supply for remote module by laser sending, in the other hand, it receives data from remote module. The output of merging units is sent to the protection and control devices using the specified protocol (IEC60044-8 protocol or TDM bus protocol).

    • Features

    The highest voltage rate of DC electronic VT is 1100kV.

    The DC electronic VT adopts HV resistor in high precision with metallic film as a voltage divider resistor. The measurement accuracy can reach Class 0.2;

    The HV side and LV side of the capacitance divider are designed with the same time constant, and thus the transformer has good frequency characteristics and transient characteristics as well as rapid response;

    The remote-end in the high voltage side is powered by laser supply. The laser power can be adjusted in real- time according to the operating situation of the remote-end module;

    The remote module is extensible, and can be flexibly combined with merging units to meet various application demands of the DC control & protection system;

    The DC electronic VT is equipped with complete self-monitoring functions to perform operation monitoring and maintenance.

    DC filter electronic CT uses the low power CTs (LPCT) to convert primary current to digital signals. DC filter electronic CT can be used for current measurement in the high voltage side, low voltage side and imbalance branch for DC filter.

    The filter electronic CT is composed of LPCTs, remote-end modules, merging units, and composite insulators with embedded optical fibers. The output signals of LPCT are processed by the remote module and transmitted via optical fibers. The filter electronic CT has the same features as the DC electronic CT does.

    log on
    phone:
    password:
    Code:
    Register
    Register
    phone:
    password:
    E-mail:
    company:
    name:
    country:
    Code:
    Previous:PCS-8300 High-voltage DC Circuit Breaker Back to list

    © Copyright NR Electric Co., Ltd.
    All Rights Reserved.

    About us Service & Support Company Training Contact Us

    Solutions Power Generation Transmission System Distribution Network Industrial Consumer

    Products Protection,Automation&Control FACTS HVDC Renewable & Microgrid