Functions
    • Tripping and closing of circuit breakers

    This device receives various GOOSE signals from protection devices, including tripping signals; both initial and non initial AR,and reclosing signals.Then the device drives corresponding output relays to convert GOOSE signals to output.

    • ŸRemote control outputs

    This device provides 33 binary outputs. In addition to tripping/closing and blocking the outputs from the circuit breaker, it also has remote control tripping, closing and blocking contacts for four disconnectors and four earth switches.There are 24 output contacts in total.

    • ŸRemote signal inputs

    This device provides 54 binary inputs. It can locally acquire binary quantities such as breaker position, switch position, and signals from thecircuit breaker mechanism and main transformer body. Then it can upload them to a corresponding protection device or BCU via GOOSE network.