Functions
    • Automatic transfer switch (ATS)

    • ŸRemote/local control function

    • ŸCircuit breaker status monitoring

    • Tripping circuit supervision (TCS)

    • ŸVT circuit supervision (VTS)

    • ŸSelf diagnostic

    • ŸVoltage drift auto adjustment

    • Ÿ64 Operation reports

    • Ÿ1024 supervision alarm records

    • Ÿ1024 control operation records

    • Ÿ1024 user operating logs

    • Ÿ64 fault and disturbance records (FDR)

    • Ÿ1024 latest SOE records

    • ŸUp to four 10Base-T/100Base-TX (RJ45) ports or two 100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for non-time-critical message, IEC 60870-5-103 over TCP/IP or DNP 3.0

    • ŸTwo RS-485 rear ports with IEC 60870-5-103

    • ŸUp to Six 100Base-FX ports with IEC 61850-9-2 Sampling Value and GOOSE for time-critical message

    • ŸOne RS-485 rear port for clock synchronization

    • ŸOne RS-232 rear port for printer

    • Ÿ1 faceplate RJ45 port for testing and setting

    • ŸClock synchronization via pulse, IRIG-B and SNTP