HOME PRODUCTS Protection&Control Transfer & Synchronization
PCS-9659 is a digital synchronizer that determines the proper time to initiate closing of the circuit breaker to parallel a generator and bus, or to reclose a line. In order to fulfill different application requirements, it offers three synchronizing modes: automatic synchronizing, semi-automatic synchronizing and manual synchronizing. By monitoring frequency, voltage and phase angle, the PCS-9659 provides correction signals to the governor of prime mover and voltage regulator of generator for voltage matching and frequency matching.
Automatic synchronizing (25A)
Semi-automatic synchronizing (25SA)
Manual synchronizing (25M)
Multi-generator paralleling solution: capability of 10 circuit breakers’ synchronization. To any of the circuit breakers, frequency and voltage regulation can be done separately.
Blocking signal to other equipment
Receive blocking signal from other equipment
Low voltage alarm at system side
Low voltage alarm at the side to be connected
PT circuit failure alarm at system side
PT circuit failure alarm at the side to be connected
Synchronous mode error alarm
Over voltage alarm at the side to be connected
Synchronization failure alarm
Synchronization counts error alarm
Remote startup error alarm
Self diagnostic
Fault Recorder
Total 1024 SOE, including closing, alarm, binary input change and human operation reports
64 closing records
Up to four 10Base-T/100Base-TX (RJ45) ports or two 100Base-FX ports with IEC 61850-8-1 MMS for non-timecritical message, IEC 60870-5-103 over TCP/IP or MODBUS TCP.
Two RS-485 rear ports with IEC 60870-5-103 or MODBUS RTU.
One RS-485 rear port for clock synchronization
One RS-232 rear port for printer
1 faceplate RJ45 port for testing and setting
Clock synchronization via pulse, IRIG-B and SNTP