The PCS-9611 relay is a protection, control and monitoring unit for various applications (such as overhead line, underground cable and transformer etc.) on solidly ground, impedance grounded, Peterson coil grounded and ungrounded system. The PCS-9611 features a high performance functional library, programmable logic, configurable I/O and integrated frequency- tracking.
The PCS-9611 is designed based on advanced multiprocessor platform, fully complying with IEC 61850 station bus & process bus, supporting IEC 61850-8-1 MMS, GOOSE and IEC 61850- 9-2 Sampling Value.
Up to four 10Base-T/100Base-TX (RJ45) ports or two 100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for non-time-critical message, IEC 60870-5-103 over TCP/IP or DNP 3.0
Two RS-485 rear ports with IEC 60870-5-103
Up to Six 100Base-FX ports with IEC 61850-9-2 Sampling Value and GOOSE for time-critical message
One RS-485 rear port for clock synchronization
One RS-232 rear port for printer
1 faceplate RJ45 port for testing and setting
Clock synchronization via pulse, IRIG-B and SNTP
Metering of current, voltage, active power, reactive power, power factor, energy, frequency, and harmonic.
Circuit breaker monitoring.
CT failure supervision.
VT failure supervision.
Line voltage failure supervision.
Tripping circuit supervision.
Self diagnostic.
Fault Recorder.
Total 1024 SOE, including tripping, alarm, binary input change and human operation reports.
Total 64 oscillograms. (Compatible with COMTRADE format)
Six-stage overcurrent protection. (67P, 50P/51P)
Six-stage neutral/ground overcurrent protection. (67G, 50/51G)
Four-stage sensitive earth fault protection. (67SG/51SG)
Two-stage undervoltage protection and two-stage over voltage protection. (27/59)
One-stage negative sequence overvoltage protection. (47)
Two-stage zero sequence overvoltage protection. (59G)
Four-stage under-frequency protection, four-stage over- frequency protection and four-stage rate-of-change of frequency (81)
Breaker failure protection. (50BF)
4-shot three-pole auto-reclosing with sync-check and dead line/bus check. (79/25)
Dead zone protection. (50DZ)
Negative sequence overcurrent protection (46)
Broken conductor detection. (46BC)
Thermal overload element. (49)
Undercurrent protection. (37)
Switch-onto-fault (SOTF) logic.
Cold load pickup logic (CLP)
Mechanical Protection
Interlocking logic for distribution busbar protection.
Remote and local tripping/closing of the breaker.
Interlocking logic of the breaker control.
Voltage and current drift auto adjustment.
Frequency tracking.
Fault locator.