  • PCS-9691 Management Relay

  • The PCS-9691 relay is a protection, control and monitoring unit for various applications (such as overhead line, underground cable, transformer and capacitor etc.) on solidly grounded, impedance grounded, Peterson coil grounded and ungrounded system. The PCS-9691 features a high performance functional library, programmable logic, configurable I/O and integrated frequency-tracking. 

    The PCS-9691 is designed based on advanced multiprocessor platform, fully complying with IEC 61850 station bus, supporting IEC 61850-8-1 MMS.

  • Send Inquiry Now

Protection
  • Six-stage phase overcurrent protection(50/51P)
  • Four-stage directional phase overcurrent protection (67P)
  • Six-stage neutral/ground overcurrent protection(50/51N, 50/51G)
  • Four-stage directional neutral/ground overcurrent protection(67N/G)
  • Two-stage negative-sequence overcurrent protection (46)
  • Thermal overload protection for alarm/trip (49)
  • Broken conduct detection (46BC)
  • Breaker failure element (50BF)
  • Dead zone protection (50DZ)
  • Undercurrent protection (37)
  • Restricted earth fault protection (64REF)
  • Two-stage phase-ground or phase-phase undervoltage protection (27)
  • Two-stage phase-ground or phase-phase overvoltage protection (59)
  • Two-stage ground overvoltage protection (59G)
  • One-stage negative sequence overvoltage protection (47)
  • Four-stage under-frequency protection (81U)
  • Over-frequency protection (81O)
  • Frequency rate-of-change protection (81R)
  • Directional power protection (32)
  • Four-shot three-pole auto-reclosing (79)
  • Synchronism check for manual closing and auto- reclosing (25)
  • Switch onto fault logic (SOTF)
  • Cold load pickup logic (CLP)
  • Mechanical protection (MR)
  • Fault location (FL)
  • Voltage and current drift auto adjustment

Control
  • Remote/Local control
  • Lock/unlock logic
  • Face plate control button

Monitoring
  • Tripping circuit supervision (TCS)
  • Voltage transformer supervision (VTS)
  • Current transformer supervision (CTS)
  • Circuit breaker status monitoring
  • Self supervision

Communication
  • Up to two 100Base-FX ports with IEC 61850-8-1 MMS for non-time-critical message, IEC 60870-5-103 over TCP/IP or DNP 3.0
  • One RS-485 rear port with IEC 60870-5-103 or Modbus
  • One RS-485 rear port for clock synchronization
  • 1 faceplate RJ45 port for testing and setting
  • Clock synchronization via pulse per second, IRIG-B and SNTP
  • High-setting and low-setting elements are provided for Restricted Earth Fault protection (REF). CT saturation detection element is integrated for the blocking of low-setting REF. The CT ratio compensation is provided to eliminate the unbalance due to CT ratio.
  • Six-stage over- & under- frequency protections and four-stage change-of-frequency (df/dt) are integrated to implement load shedding and other control schemes. The over- & under- frequency protection is controlled by voltage element to avoid the mal-operation due to short-circuit faults.
  • Cold load pickup logic is integrated to automatically increase the setting of phase overcurrent and zero sequence overcurrent protections to improve the adaptability for various loads.
  • Fault locator function is integrated for the post-fault checking and maintenance.
  • Dead zone protection is integrated to clear the faults between the CT coil and the circuit breaker.
  • Directional power element is provided for the reverse power protection or forward power protection.
  • Thermal model based on IEC60255-8 standard is integrated for thermal overload protection. The fundamental current and 2nd to 7th harmonics are utilized for thermal accumulation.
  • Broken conduct protection can be automatically blocked for a very short time to avoid the mal-operation due to the circuit breaker switching.
  • Up to six stages of phase overcurrent protection are provided for various applications. Four stages can be controlled by directional element, harmonic blocking element and voltage element (phase-phase undervoltage or negative sequence overvoltage)
  • Up to six stages of neutral/ground(zero sequence) overcurrent protection are integrated. Four stages can be controlled by directional element and harmonic blocking element.
  • 12 IDMT curves are integrated: five IEC curves (short time inverse, standard inverse, very inverse, extremely inverse, long time inverse), six IEEE/ANSI curves (short time inverse, moderately inverse, inverse, very inverse, extremely inverse, long time inverse) and one self-defined curve.
  • Self-adaptive polarized voltage is employed for directional element to avoid the mal-operation due to the close-in severe three-phase faults. The memorized voltage or measured voltage is automatically selected according to different scenario.
  • Independent phase overcurrent element and zero sequence overcurrent element are employed for the Switch-Onto-Fault (SOTF) logic to achieve the high-speed tripping.
  • Phase-ground voltage or phase-phase voltage can be selected for overvoltage and undervoltage protections. Selective 1-phase (‘OR’ logic) and 3-phase (‘AND’ logic) modes are supported.
  • Up to 13th harmonics are measured for power quality monitoring.
  • Four self-definable buttons are provided in the face-plate for easy control and maintenance. The button can be set as the remote/local, lock/unlock, open/close for the circuit breaker control.
  • Powerful disturbance recording function is integrated in the relay for after-fault analysis. Up to 64 disturbance reports can be stored in non-volatile memory. Each report includes 5-cycle pre-fault waveform and 100-cycle to 416-cycle post-fault waveform.